The Siemens S7 driver talks to Siemens S7 PLCs over S7comm, the classic Step 7 protocol carried on ISO-on-TCP. It uses absolute addressing — memory area, data-block number, byte and bit — so it works without any symbol export from the engineering project. Add a device under the Siemens S7 driver in the Connector and fill in the fields below; the panel shows only the fields this protocol uses.

Connection

Field Meaning Default
Host IP address or host name of the CPU (or of the CP module that fronts it). empty
Rack / Slot The CPU's rack and slot numbers, as configured in the Siemens hardware layout. Two number boxes on one row: rack first, slot second. 0 / 0
Poll interval (ms) Device-wide read period for tags that do not override it. 1,000

The TCP port is fixed at 102 (ISO-on-TCP), so there is no port field. The device header shows the assembled endpoint, for example s7://192.168.0.2:0:1 (host, rack, slot).

Rack and slot must match the hardware: S7-1200 and S7-1500 CPUs answer on rack 0, slot 0 or 1; a typical S7-300 CPU sits at rack 0, slot 2; S7-400 racks vary with the layout. A wrong slot fails the connection rather than reading wrong data.

Each tag may set its own Poll interval (ms); a tag value of 0 falls back to the device interval.

Addressing

An S7 tag is addressed by typed fields, not by a free-text string. The panel shows them in the tag's Source card:

Field Meaning Accepted values Default
Area The memory area to read. DataBlock, Merker, ProcessInput, ProcessOutput, Timer, Counter DataBlock
DB number Which data block, shown only when Area is DataBlock. 0 and up 1
Start byte Byte offset inside the area where the value starts. In the Timer and Counter areas the box is labelled Timer number or Counter number and asks for the number of the timer or counter instead. 0 and up 0
Bit (0–7) Bit position inside the start byte. Shown only for Boolean tags. 0–7 0
Max length (blank = 254) Declared maximum of an S7 STRING. Shown only for String tags outside the Timer and Counter areas. 1 and up, blank blank

The areas map to the usual Siemens notation: Merker is flag memory (M), ProcessInput the process-image inputs (I/E), ProcessOutput the process-image outputs (Q/A), and Timer/Counter the S7 timer and counter areas. Timers and counters are addressed by number, not by byte: Timer with the number 5 reads T5, and Counter with the number 3 reads C3. Translating classic absolute addresses:

Classic address Data type Fields to enter
DB5.DBD12 holding a REAL Float Area DataBlock, DB number 5, Start byte 12
DB1.DBX3.4 Boolean Area DataBlock, DB number 1, Start byte 3, Bit 4
DB2.DBW20 holding an INT Int16 Area DataBlock, DB number 2, Start byte 20
MW10 Int16 Area Merker, Start byte 10
M10.3 Boolean Area Merker, Start byte 10, Bit 3
IB2 Byte Area ProcessInput, Start byte 2
Q4.1 Boolean Area ProcessOutput, Start byte 4, Bit 1
T5 Int16 Area Timer, Timer number 5
C3 Int16 Area Counter, Counter number 3

A Boolean tag reads and writes exactly one bit on the wire; it never rewrites the surrounding byte. Every other type is byte-addressed at the start byte with the exact width of its data type. The Source card's read-only Source address (wire) line shows the assembled address as you edit.

Data types

The tag's Data type decides the S7 native type on the wire. All thirteen S7-native widths are available:

Data type S7 type Size on the wire
Boolean BOOL 1 bit
SByte SINT 1 byte
Byte USINT 1 byte
Int16 INT 2 bytes
UInt16 UINT 2 bytes
Int32 DINT 4 bytes
UInt32 UDINT 4 bytes
Int64 LINT 8 bytes
UInt64 ULINT 8 bytes
Float REAL 4 bytes
Double LREAL 8 bytes
String STRING max length + 2 bytes
DateTime DTL 12 bytes

Multi-byte values use the S7-native big-endian byte order automatically; there is no byte-order option because none is needed.

A String tag reads the standard S7 STRING layout: one byte of declared maximum, one byte of current length, then ASCII characters. Max length must match the STRING declaration in the block (blank means the S7 maximum of 254); the driver transfers max length + 2 bytes per read. A DateTime tag maps to the DTL structure of the S7-1200/1500 family (year through nanoseconds); the older 8-byte DATE_AND_TIME is not offered.

Writes

Tags whose Access is Read and write or Write only can be written. Writes address the same area, byte and bit as reads: a Boolean write sets its single bit, everything else writes the type's exact bytes. A new tag starts as Read only.

Discovery

S7comm has no broadcast discovery, so the Connector shows no Discover button for this driver. Add the device and its tags by hand.

Good to know

  • On S7-1200/1500 CPUs, S7comm's absolute addressing requires two settings in the Siemens project: Permit access with PUT/GET communication on the CPU, and optimized block access switched off on every data block you address. An optimized DB has no byte offsets to address.
  • The Timer and Counter areas are addressed by number, not by byte offset: the box asks for the timer or counter itself (T0, T1, T2 and C0, C1, C2). Each value is one 16-bit word, so pair it with Int16; a wider or narrower data type is refused with the tag named in the journal, and the device's other tags keep reading.
  • An unreachable PLC costs nothing at startup: the device keeps retrying in the background and its tags read as bad quality until the connection lands.
  • A cable pulled after the device is online is noticed on the next read: the device goes offline, its tags turn bad quality, and it reconnects on its own once the network is back. An address the CPU refuses does not do that, so one mistyped tag never takes the rest of the device down with it.